All posts by cagodsy

Do I have to email the site a new copy of the client software every time I want to log in or is this a service that permanently runs?

Q:  Do I have to email the site a new copy of the client software every time I want to log in or is this a service that permanently runs?

A: Email the client software one time to each site. The exception to this would be if you wanted to give the site a newer version of the client software. The client software copy can be put on unlimited site computers, but only run one client software copy at any time because the support connection is for one at a time. Running one support client at a time is true across all sites. The client software runs as a java application which must be started and stopped, and does not run as a service.  (see How to Get the latest version of Java)


How to get the latest version of software?

Q: How to get the latest version of software?

A: The gateway will automatically check for an update of the software every time it boots up.  If it needs an update, then it will update automatically.  Versions of software can be checked by viewing the from the Manage connections screen.

The latest versions of the Field Client software used at the remote customer site can be downloaded once your logged in.   Just click on the Download menu item as shown below.

Download Menu Item


 

TCP Ports used by PLC’s ( Programmable Logic Controllers) and HMI/ OIT’s

List of TCP port numbers used by commercial equipment controllers:

  • Allen Bradley – All newer Rockwell PLC’s : 44818 (See List Below for more details)
  • Allen Bradley – Older Rockwell AB PLC5E and SLC5/05 use TCP 2222
  • BECKHOFF Embedded PC: 48898
  • C-more HMI Programming: 9999
  • Danfoss ECL Apex: 5050
  • FATEK FB Series: 500
  • GE Fanus Series 90-30: 18245
  • GE SRTP uses TCP ports 18245 and 18246
  • GE QuickPanels use TCP port: 57176
  • HITACHI EHV Series: 3004
  • KEYENCE KV-5000: 8501
  • Korenix 6550: 502
  • Koyo Ethernet: 28784
  • LS GLOFA FEnet: 2004
  • LS XGB FEnet: 2004
  • LS XGK FEnet: 2004
  • Memobus (Yaskawa MP Series Controllers): 502
  • Mitsubishi FX: 1025
  • MITSUBISHI FX3u (Ethernet): 5001
  • MITSUBISHI MELSEC-Q (Ethernet): 4999
  • MITSUBISHI MR-MQ100 (Ethernet): 4999
  • MITSUBISHI QJ71E71 (Ethernet): 5002
  • MODBUS TCP/IP (Ethernet): 502
  • MODBUS Server (Modbus RTU Slave): 502
  • Omron PLC: 9600
  • Panasonic FP (Ethernet): 9094
  • Panasonic FP2 (Ethernet): 8500
  • Parker Drives using MODBUS TCP/IP (Ethernet): 502
  • Red Lion HMI’s:  789
  • SAIA S-BUS (Ethernet): 5050
  • Schleicher XCX 300: 20547
  • Siemens S7 protocol uses TCP port: 102
  • Toshiba Series PLC’s uses Modbus port: 502
  • Trio (MODBUS RTU, TCP/IP): 502
  • Unitronics Socket1 – TCP slave: 20256
  • Unitronics Socket2 – TCP slave: 502
  • Unitronicsw Socket3 – TCP slave: 20257
  • Wago CODESYS – TCP: 2455
  • YAMAHA NETWORK BOARD Ethernet RCX series uses telnet port: 23
  • YASKAWA MP Series Ethernet: 10000
  • YASKAWA MP2300Siec: 44818
  • YASKAWA SMC 3010 (Ethernet): 23
  • Yokogawa FA-M3 (Ethernet): 12289

 

Newer Rockwell Allen Bradley Detailed Equipment List for TCP Port 44818
1756-ENET
1756-ENBT
1756-EWEB
1794-AENT
1734-AENT
1769-L35E, 1769-L32E
1788-ENBT
1761-NET-ENI
1785-LXXE
1785-ENET
1747-L55x
1763-L16x
1766-L32x
PowerMonitor 1000
PowerMonitor 3000
PowerMonitor 5000
PanelView
RSLinx Classic
RSLinx Enterprise
INTERCHANGE (rsicd)

Older Rockwell Allen Bradley Equipment List TCP Port 2222
1785-Lxxe
1785-ENET
1771-DMC(x)
1747-L55x
5820-EI
PowerMonitor II
INTERCHANGE
PowerMonitor 1000
PowerMonitor 3000
PowerMonitor 5000
RSLinx Classic